In the UAE, Cabinet Resolution No. 24 of 2012 obliges building and facility owners to maintain fire safety systems regularly through Civil Defence-accredited companies and to subscribe to electronic monitoring linking buildings to Civil Defence. Tampering with an automatic fire suppression system carries an AED 10,000 fine. Public sector contracts in Dubai specify Civil Defence approval, quarterly preventive maintenance and 24/7 emergency response. The UAE Fire and Life Safety Code of Practice, updated in 2018, defines responsibilities for owners, tenants and maintenance companies.
Why fire safety maintenance is a legal duty in Dubai, not an option
In most building systems, poor maintenance costs money. In fire safety, it can cost lives, and in the UAE it is also a legal obligation. Under Cabinet Resolution No. 24 of 2012 regulating Civil Defence services, facility and building owners are obligated to carry out regular maintenance of their fire safety systems through companies accredited by the Civil Defence authority, and to subscribe to an electronic monitoring system that links buildings to Civil Defence operations rooms. Gulf News reported these obligations as Abu Dhabi Civil Defence Authority reminded owners of the federal resolution; Dubai Civil Defence implemented the same resolution in Dubai.
The resolution also carries teeth. According to that report, modifying, disconnecting, removing or covering any component of an automatic fire suppression system carries a fine of AED 10,000; a facility that lacks proper fire prevention measures and firefighting equipment during an incident may be charged up to AED 50,000 to cover firefighting and rescue costs; and non-compliant facilities can be closed until violations are fixed. When Dubai Civil Defence implemented the resolution, fines were reported to range from AED 500 to AED 50,000 depending on the degree of danger, with homes or independent houses of a non-commercial nature exempt from that resolution.
The practical message for any owner or manager of a commercial or residential building in Dubai: fire safety maintenance must be continuous, documented, and carried out by the right company.
The rules that govern fire safety in Dubai buildings
| Instrument | What it does |
|---|---|
| Cabinet Resolution No. 24 of 2012 | Regulates Civil Defence services; obliges owners to maintain fire safety systems through accredited companies and subscribe to electronic monitoring; sets fines |
| UAE Fire and Life Safety Code of Practice | The technical code issued by the General Command of Civil Defence, Ministry of Interior; major update in 2018, including a chapter on the responsibilities of stakeholders |
| Hassantuk | The Ministry of Interior's smart monitoring system linking fire alarms to an Alarm Receiving Centre; mandatory for villas under the national programme |
| Dubai Civil Defence inspection and enforcement | Inspections, warnings and fines for fire safety violations in Dubai |
The UAE Fire and Life Safety Code: what owners need to know
The UAE Fire and Life Safety Code of Practice, issued by the General Headquarters of Civil Defence at the Ministry of Interior, is the technical reference for fire safety in UAE buildings. It covers design, construction, fire detection and alarm systems, fire protection systems, smoke control and more, with an entire chapter on fire detection and alarm systems.
The 2018 edition added a chapter titled "Responsibilities of Stakeholders", which, as described in MEED, defines the responsibilities of the client or owner, the designer or consultant, the contractor, the equipment supplier and the maintenance company, among others. When the updated code was introduced, The National reported that its responsibility section placed obligations on consultants and developers as well as residents, owners and tenants, and that changes included annual renewal of no-objection certificates by building owners and a focus on third-party inspections.
The code and other GCC codes are based on international standards and practices, and fire safety systems must be tested and maintained at the intervals those codes and standards describe. In practice, maintenance programmes in Dubai follow the code together with the referenced international standards for each system.
What Dubai's own public sector asks for in a fire safety AMC
A useful way to see what a serious fire safety maintenance contract looks like in Dubai is to read how public bodies specify one. Requests for quotation published by the Dubai Electricity and Water Authority (DEWA) for annual maintenance of fire alarm, firefighting and emergency lighting systems at its sites include requirements such as:
- approval from Dubai Civil Defence for the maintenance of fire protection systems;
- preventive maintenance carried out quarterly, with a minimum of four services in the year;
- emergency maintenance calls attended 24 hours a day, 7 days a week;
- the maintenance contract agreement and safety certificate obtained from Dubai Civil Defence;
- both preventive activities and corrective maintenance within scope;
- refilling and repair of fire extinguishers;
- a snag list submitted once the contract is awarded;
- an ISO-certified service provider.
These specifications cover systems such as the fire alarm system, fire pumps, portable fire extinguishers, landing valves and hydrants, and gas suppression and foam systems. They are a good benchmark for any building owner comparing fire safety maintenance offers.
Hassantuk: the smart fire alarm monitoring system
Hassantuk ("Protect You" in Arabic) is the UAE Ministry of Interior's smart monitoring, alert and control system, unveiled with Injazat Data Systems. It connects buildings and facilities to an automated alarm-receiving centre that can request immediate dispatch of Civil Defence for fire and other life-threatening incidents. At its launch, officials said Civil Defence would be aware of any fire or life-safety emergency in less than 120 seconds.
Hassantuk for villas
The national programme made fire alarms connected to Hassantuk mandatory for villas. Reporting on the deadline, The National quoted a ministry official confirming that the homeowner, not the tenant, is responsible for installing the fire alarm system, and that owners must sign up to the Hassantuk e-alert system. The decision followed fire incidents including the death of a baby in a Dubai house fire in July 2019.
Hassantuk in Dubai
Dubai Civil Defence has reported linking homes to the system: in 2020, Gulf News reported that more than 2,600 houses in Dubai were linked to the Hassantuk smart fire alarm system, which connects fire alarms and smoke detectors to a centralised Alarm Receiving Centre. The same report noted 306 fires in Dubai in 2019, about 95 percent of them minor, a five percent decrease on the previous year, and a response time of four minutes, with officials crediting smart monitoring and linking buildings to an alert system. Because requirements and connection processes can differ by property type, confirm the current requirement for your property with Dubai Civil Defence.
Why maintenance still matters with monitoring
Monitoring only works if the system it monitors works. A detector covered in dust, a disconnected sounder or a panel showing faults may still be connected to a monitoring centre, but it will not protect anyone. False alarms are another cost: in Abu Dhabi, Gulf News reported that half of 2,500 fire alarms triggered through Hassantuk in one period were false. Regular testing and cleaning reduce both missed fires and false alarms.
Which fire safety systems need maintenance
| System | What maintenance covers |
|---|---|
| Fire detection and alarm system | Control panel, detectors, manual call points, sounders and beacons, batteries, cabling faults, interfaces with other systems and the monitoring connection |
| Sprinkler system | Valves, gauges, alarm devices, heads, pipework and test of flow and alarms |
| Fire pumps | Electric main pump, jockey pump and diesel pump where installed; controllers, run tests and fuel for diesel pumps |
| Hose reels, landing valves and hydrants | Pressure, valves, hoses, nozzles, cabinets and signage |
| Portable fire extinguishers | Inspection, pressure check, refilling, repair and replacement |
| Gas suppression systems | FM200, Inergen and similar systems protecting server rooms and critical spaces: cylinders, detection, controls and room integrity |
| Kitchen hood suppression | Wet chemical systems over cooking equipment, nozzles, fusible links and release mechanisms |
| Emergency and exit lighting | Lamps, batteries, duration tests and signage |
| Fire doors and compartmentation | Closers, seals, hardware, and doors kept closed and unobstructed |
| Smoke control systems | Fans, dampers, controls and their interface with the alarm system |
| Public address and voice evacuation | Speakers, amplifiers and message tests |
Fire water tanks and pumps are also part of the picture: Dubai Civil Defence has described monitoring elevators, control panels, fire pumps, water tanks and building gas systems through its smart mechanism linking buildings across the emirate.
What a quarterly preventive visit should include
Quarterly preventive maintenance is the benchmark in the public sector specifications above. A proper visit should leave a written record of:
- Fire alarm panel: fault and event log review, battery condition, indicators, power supplies.
- Detection devices: a planned rotation of detector and call point testing, so that devices across the building are tested over the year.
- Sounders and beacons: audibility and visual signal checks in the zones tested.
- Interfaces: lift homing, smoke control, door releases, gas shut-off and other cause-and-effect functions.
- Fire pumps: run test, pressures, controllers and, for diesel pumps, fuel, batteries and coolant.
- Sprinklers: valve positions, gauges, alarm valve test and visible heads free of paint or obstruction.
- Hose reels and landing valves: pressure, condition and access.
- Extinguishers: location, pressure, seals and service dates.
- Emergency lighting and exit signs: function and battery duration checks as scheduled.
- Report: defects found, defects fixed, defects needing approval, and the date of the next visit.
How Dubai Civil Defence enforces fire safety
Dubai Civil Defence inspects buildings and acts on violations. Gulf News has reported that the authority lists 185 types of fire safety violations, that building owners found in violation are served a warning to fix it within 10 days, and that ignored warnings lead to fines under the law, ranging from AED 500 for ill-maintained fire extinguishers up to AED 50,000 for the most serious technical violations. The same report described inspectors using electronic devices so that logs are updated immediately, and many buildings connected to a 24/7 direct alarm system.
The details of enforcement evolve, but the pattern is consistent: inspection, warning, deadline, fine, and in serious cases closure. The best protection is a maintenance programme that finds and fixes defects before an inspector does.
Who is responsible for what
Building owners and owners associations
Owners carry the core legal duty to maintain fire safety systems through accredited companies and keep monitoring in place. In jointly owned buildings, common fire safety systems are maintained through the owners association and management company, funded by service charges approved by RERA.
Facility and building managers
Managers run the programme day to day: contracts, access for technicians, fault follow-up, records, and coordination with Civil Defence inspections.
Tenants and occupants
The 2018 code places responsibilities on residents as well as owners. In practice, occupants must not cover, remove or disable detectors, block exits or fire doors, wedge fire doors open, store items in escape routes or in front of hose reels, or modify fire systems during fit-outs without approval. Tampering with an automatic fire suppression system carries a fine of AED 10,000 under Cabinet Resolution No. 24 of 2012 as reported by Gulf News.
Maintenance companies
The maintenance company is named among the stakeholders whose responsibilities the 2018 code defines. Its job is to maintain the systems to the code and referenced standards, report defects honestly, and keep records the owner can show inspectors.
Fire safety by type of property
Residential towers
Fire alarm and detection across apartments and common areas, sprinklers, fire pumps and tanks, hose reels and landing valves, smoke control in high-rise buildings, emergency lighting and voice evacuation. Detectors inside apartments are often the weak point, because access depends on residents. Planned access schedules and resident communication are part of a good programme.
Villas
Smoke and heat detectors connected to a monitored system under the Hassantuk villa programme, plus extinguishers and, in larger villas, more extensive systems. The ministry has said the homeowner is responsible for installing the system.
Offices
Alarm and detection, sprinklers, extinguishers, emergency lighting, and gas suppression for server rooms. Fit-outs frequently move partitions and ceilings, which can leave detectors and sprinklers in the wrong places.
Restaurants and commercial kitchens
Kitchen hood suppression systems, extinguishers suitable for cooking oil fires, alarm interfaces, and gas shut-off. Kitchen exhaust grease is a major fire load; our kitchen exhaust and grease trap guide covers cleaning frequencies under NFPA 96.
Hotels
Large alarm systems with many devices in guest rooms, voice evacuation, sprinklers, kitchens and laundry areas, and constant occupancy, which makes testing schedules and guest communication important.
Warehouses and industrial units
Sprinklers suited to storage height and type, hydrants, extinguishers, and housekeeping that keeps sprinkler heads and escape routes clear.
Schools, clinics and nurseries
Occupants who may need help to evacuate, which makes reliable alarms, clear routes, emergency lighting and drills especially important. Hassantuk was initially focused on priority buildings including schools, hospitals and public places.
The most common fire safety failures we see in buildings
- Panels in fault for weeks: faults become "normal" and real alarms are ignored.
- Detectors covered or removed during painting or fit-out and never restored.
- Fire doors wedged open or with broken closers.
- Extinguishers missing, discharged or out of date.
- Sprinkler heads painted over or blocked by storage.
- Fire pumps left in manual or with diesel tanks low.
- Hose reels blocked by stored goods or furniture.
- Emergency lights with dead batteries.
- Fit-out changes to ceilings and partitions without updating detection and sprinkler coverage.
- No records to show what was tested and when.
False alarms: why they happen and how to reduce them
False alarms waste emergency resources and teach occupants to ignore alarms. Gulf News has reported that maintenance failures and excess dust can trigger fire alarms. Common causes include dirty or old detectors, the wrong detector type for the space (for example smoke detectors near kitchens or bathrooms), cooking fumes, steam, construction dust, and faulty wiring. Reducing false alarms means regular cleaning and testing of detectors, correct detector selection, protecting detectors during works, and investigating every alarm to find its cause.
Fit-outs, renovations and fire safety
Many fire safety problems are created during fit-outs. Moving walls, lowering ceilings, adding rooms or changing use can leave areas without detection or sprinkler coverage, block escape routes or change the fire load. Before any works that affect fire systems, check the Civil Defence approval requirements with your consultant and building management, and make sure the fire contractor updates the system and records afterwards. During works, detectors are often covered to avoid false alarms from dust; covers must be removed at the end of each working day or as the building's procedures require.
How to choose a fire safety maintenance company in Dubai
- Accreditation: the law requires maintenance through companies accredited by Civil Defence. Ask for the company's accreditation and trade licence, and check them.
- Scope per system: the contract should list every system and device type covered.
- Visit frequency: at least the frequency your systems require; public sector specifications in Dubai use quarterly preventive maintenance as a minimum.
- Emergency response: 24/7 attendance for emergency calls, with defined response times.
- Civil Defence documents: who obtains the maintenance contract agreement and safety certificate from Civil Defence.
- Extinguisher service: refilling, repair and replacement included or clearly priced.
- Reports: a written report after every visit with defects and actions.
- Quality system: public specifications ask for ISO certification; ask about the company's quality and HSE systems.
- Snag list at start: an initial survey and snag list so existing defects are recorded before the contract begins.
The fire safety records every building should keep
- Fire safety system drawings and cause-and-effect matrix.
- Valid maintenance contract with an accredited company.
- Civil Defence certificates and approvals for the building and its systems.
- Reports from every preventive and corrective visit.
- Fire alarm panel event and fault logs.
- Extinguisher service records.
- Fire pump run test records.
- Emergency lighting test records.
- Fire drill and evacuation records.
- Defect lists, approvals and close-out dates.
When an inspector arrives, these records are what show that the building is maintained, not just equipped.
Fire safety as part of building maintenance
Fire safety does not stand alone. Electrical faults are a common cause of fires; kitchen exhaust grease feeds kitchen fires; blocked corridors and broken doors compromise escape; water tanks and pumps supply firefighting systems. Officials have said large blazes have been caused by broken fire alarms or defective anti-fire systems, bad electrical equipment or wiring. A maintenance programme that looks after electrical panels and safety devices, kitchen exhaust systems and pumps alongside the fire systems reduces risk across the building. For a complete picture of commercial compliance, see our commercial building maintenance guide, and for contract structure our annual maintenance contract guide.
A fire safety calendar for building managers
| When | What |
|---|---|
| Daily | Check the fire alarm panel for faults; keep escape routes, fire doors and hose reels clear |
| Weekly | Walk-through of exits, extinguishers and fire doors; confirm fire pumps are in automatic |
| Quarterly | Preventive maintenance visit by the accredited contractor, as public sector specifications in Dubai require |
| Annually | Full-year cycle of device testing completed; renewal of certificates and approvals as required; review of the maintenance contract |
| After any works | Confirm detectors and sprinklers restored, systems updated, records amended |
| After any alarm | Investigate the cause, record it, and fix the reason for false alarms |
What residents and employees can do every day
- Never cover or remove a smoke detector, even when cooking or painting.
- Never wedge a fire door open.
- Keep corridors, stairs and exits clear of storage.
- Know where the nearest extinguisher and exit are.
- Report faults: beeping detectors, damaged call points, missing extinguishers.
- Take every alarm seriously and evacuate.
- Answer the verification call if your home is connected to a monitoring system.
Fire safety and insurance
Fire safety compliance affects more than fines. When Dubai Civil Defence implemented Resolution No. 24 of 2012, it was reported that companies would need a valid certificate relating to fire safety requirements from the authority to obtain insurance. For businesses, that links fire safety maintenance directly to the ability to insure premises and stock. After an incident, insurers and investigators will look at whether systems were maintained, so maintenance records protect both people and claims.
Fire extinguishers: types and where they belong
Extinguishers are the first line of response, but only if the right type is in the right place and in working order:
- Water: for ordinary combustibles such as paper, wood and fabric; not for electrical equipment or cooking oil.
- Foam: for ordinary combustibles and flammable liquids.
- Carbon dioxide (CO2): commonly placed near electrical equipment and server rooms, because it leaves no residue.
- Dry powder: multi-purpose, widely used in car parks, plant rooms and vehicles; it leaves residue and reduces visibility indoors.
- Wet chemical: designed for cooking oil and fat fires in kitchens.
Every extinguisher needs a visible, accessible location, an intact seal and pin, a readable gauge where fitted, and an up-to-date service label. Discharged or damaged units must be refilled or replaced immediately, which is why public sector contracts in Dubai include refilling and repair in the scope.
Fire drills and evacuation planning
Systems detect and suppress fires; people still have to get out. A building's fire safety plan should include clear evacuation routes and assembly points, trained fire wardens on each floor, procedures for people who need assistance, regular drills, and a record of each drill with lessons learned. Drills also test the systems: whether alarms are heard in every area, whether doors release, and whether lifts return to the ground floor as designed. Problems found in a drill should go straight onto the maintenance defect list.
High-rise buildings: what makes them different
Tall buildings depend on systems that keep escape routes usable and support firefighters: pressurised stairs and smoke control, fire pumps that deliver water to upper floors, landing valves on each level, voice evacuation, and fire-fighting lifts where provided. These systems interact through the cause-and-effect programme of the fire alarm panel. Maintenance in towers must test those interactions, not just individual devices, because a detector that works but fails to start the stair pressurisation fans leaves the building unsafe.
Summer, heat and fire risk
Dubai's summer adds load to building systems that can raise fire risk: electrical circuits carrying heavy air conditioning loads, batteries in fire panels and emergency lights ageing faster in hot plant rooms, and diesel fire pump rooms running hot. Before summer, include electrical panel checks, battery condition checks and fire pump room inspections in the maintenance plan.
When the fire alarm panel shows a fault
A fault is not an alarm, but it means part of the system may not work when needed. Treat every fault as urgent:
- Read and record the fault message, zone and time.
- Do not silence and forget it. Silencing the buzzer does not clear the problem.
- Check for obvious causes: works in the zone, a removed detector, a damaged call point, water ingress.
- Call the maintenance company and log the call.
- Keep the fault in the building log until it is fixed and the panel returns to normal.
- If a whole zone or the panel is out of service, put temporary measures in place as advised by the contractor and building management, such as additional patrols, until it is restored.
Comparing fire safety maintenance quotes
Fire safety quotes vary widely because scope varies widely. Put every offer into the same frame before comparing prices:
| Question | Offer A | Offer B |
|---|---|---|
| Civil Defence accreditation provided | ||
| Systems and device counts covered | ||
| Preventive visits per year | ||
| Emergency response time, 24/7 | ||
| Civil Defence documents handled | ||
| Extinguisher refilling and replacement | ||
| Parts and batteries included or priced | ||
| Written report after each visit | ||
| Initial survey and snag list | ||
| Annual price and payment terms |
A low price that leaves out device testing, extinguisher service or emergency response is not a saving; it is a gap that an inspector or a fire will find.
Gas suppression systems in server rooms and critical spaces
Server rooms, telecom rooms, archives and some electrical rooms are often protected by clean agent gas systems such as FM200 or Inergen, which public sector specifications in Dubai include in their fire safety maintenance scope. These systems work by filling a closed room with agent at the right concentration, which means they depend on more than the cylinders. Maintenance should cover cylinder pressure or weight checks, detection and control panels, manual release and abort switches, warning signs and lights, and the integrity of the room itself. A new cable opening in a wall, a door that no longer closes properly or a removed ceiling tile can let the agent escape and leave the room unprotected. Any works in a protected room should be coordinated with the fire contractor so the system is isolated safely during the works and restored afterwards.
Common questions building owners ask about fire safety contracts
Is a fire safety maintenance contract required if my systems are new?
Yes. The obligation under Cabinet Resolution No. 24 of 2012 is regular maintenance through an accredited company, regardless of the age of the systems. New systems also have commissioning records and warranties that depend on proper maintenance.
Can my general maintenance company handle fire systems?
Only if it is accredited by Civil Defence for fire safety maintenance. A general maintenance company can coordinate the work, but the fire systems must be maintained by an accredited company.
What happens to defects found during maintenance?
They should be listed in the visit report, quoted if outside the contract scope, approved, fixed and closed out with a record. Unresolved defects are exactly what inspections find.
Firefighting system maintenance with Power Zone
Power Zone is a building services company with its head office in Court 2203, Office 149, Business Bay, Dubai, operating under ZONE15 Technical Services L.L.C (Commercial License No. 1289514). Power Zone and Zone 15 are one business family under the same management; you can read more on our About page.
Our firefighting system maintenance service sits alongside electrical, plumbing, pump, kitchen exhaust and general building maintenance, so fire safety is managed as part of the whole building rather than in isolation. Every job follows the same path: your request, a site survey, an itemised proposal you approve before work starts, the work, and handover with a written report. Request a site survey.
Frequently asked questions
Is fire safety maintenance mandatory in Dubai?
Yes. Under Cabinet Resolution No. 24 of 2012, building and facility owners must carry out regular maintenance of fire safety systems through Civil Defence-accredited companies and subscribe to electronic monitoring linking buildings to Civil Defence.
What is the fine for tampering with fire safety systems in the UAE?
Modifying, disconnecting, removing or covering any component of an automatic fire suppression system carries a fine of AED 10,000 under Cabinet Resolution No. 24 of 2012, as reported by Gulf News.
What fines does Dubai Civil Defence issue?
When Dubai Civil Defence implemented Resolution No. 24 of 2012, fines were reported to range from AED 500 to AED 50,000 depending on the degree of danger. Gulf News has reported that owners are first warned to fix violations within 10 days.
How often should fire safety systems be maintained in Dubai?
Public sector fire safety contracts in Dubai, such as DEWA's, specify quarterly preventive maintenance with at least four services a year, plus 24/7 emergency response. Detailed test intervals follow the UAE Fire and Life Safety Code and its referenced standards.
What is Hassantuk?
Hassantuk is the UAE Ministry of Interior's smart fire alarm monitoring system. It links fire alarms to an Alarm Receiving Centre that can dispatch Civil Defence; officials said at launch that Civil Defence would know of an emergency in under 120 seconds.
Is Hassantuk mandatory for villas?
The national programme made monitored fire alarms mandatory for villas, and a ministry official told The National the homeowner, not the tenant, is responsible for installation. Confirm the current requirement for your property with Dubai Civil Defence.
Who is responsible for fire safety in a rented apartment?
Owners and owners associations maintain the building's fire systems. Tenants must not cover, remove or disable detectors, block exits or wedge fire doors open. The 2018 UAE fire code places responsibilities on owners and tenants alike.
What is the UAE Fire and Life Safety Code of Practice?
The technical fire safety code issued by the General Command of Civil Defence, Ministry of Interior. Its 2018 edition added a chapter defining responsibilities of owners, consultants, contractors, suppliers and maintenance companies.
What should a fire safety maintenance contract include?
Every system and device covered, visit frequency, 24/7 emergency response, Civil Defence documentation, extinguisher service, written reports, an initial snag list, and the company's Civil Defence accreditation.
Which fire safety systems need maintenance?
Fire alarm and detection, sprinklers, fire pumps, hose reels and landing valves, extinguishers, gas suppression, kitchen hood suppression, emergency lighting, fire doors, smoke control and voice evacuation systems.
Why does our fire alarm keep giving false alarms?
Common causes are dirty or old detectors, wrong detector types for the space, cooking fumes, steam, construction dust and faulty wiring. Regular cleaning, testing and investigating every alarm reduces them.
Can a general maintenance company maintain fire systems?
Only if it is accredited by Civil Defence for fire safety maintenance. The law requires fire systems to be maintained through accredited companies.
What records should a building keep for fire safety?
System drawings, the maintenance contract, Civil Defence certificates, visit reports, panel logs, extinguisher, pump and emergency lighting test records, drill records and defect close-outs.
Do fit-outs affect fire safety?
Yes. Moving walls and ceilings can leave areas without detection or sprinkler coverage. Check Civil Defence approval requirements before works and have the fire contractor update systems and records afterwards.
Does Power Zone provide firefighting system maintenance in Dubai?
Yes. Power Zone provides firefighting system maintenance in Dubai alongside electrical, plumbing, pump, kitchen exhaust and general building maintenance.
How do I request a fire safety maintenance proposal from Power Zone?
Send a request through the contact page or WhatsApp. We arrange a site survey and send an itemised proposal for your approval before work starts.
Sources
- Gulf News: Cabinet Resolution No. 24 of 2012, accredited maintenance, monitoring and fines
- Business Insurance: Dubai Civil Defence implementation of Resolution No. 24 of 2012 and fine range
- MEED: the 2018 UAE fire code and its Responsibilities of Stakeholders chapter
- The National: updated UAE fire code responsibilities, NOC renewal and third-party inspection
- Gulf News: launch of Hassantuk by the Ministry of Interior
- The National: mandatory fire alarms in villas and homeowner responsibility
- Gulf News: Dubai fire statistics and homes linked to Hassantuk
- Gulf News: Dubai Civil Defence inspections, warnings and fines
- Gulf News: building maintenance, false alarms and the UAE fire code
- Gulf News: Dubai Civil Defence monitoring of building systems and tenant responsibilities
- The National: causes of large blazes and maintenance duties
- Report republished from Gulf News: false alarms through Hassantuk
- DEWA: request for quotation, annual maintenance of fire alarm, firefighting and emergency lighting systems